Critical PowerModifications reserved Page 89/146GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx User Manual TLE Series 600 & 800 CE S1Code Message Description4604 COMMAND IEMi ONThe IEMi Operation Mode function is enabled, andaccording to the time program the UPS system willrun in IEMi Operation Mode.4605 COMMAND IEMi OFF The IEMi Operation Mode has been disabled or theprogrammed time is expired.4606 eBoost/IEMi ACTIVATION ALLOWEDeBoost/IEMi control signal has been cleared on theCustomer Interface Board (X1 - 11, 22).Operating mode depends on scheduled activationof the functions.4607 eBoost/IEMi ACTIVATION INHIBITEDCustomer Interface Board (X1 - 11, 22) received aneBoost/IEMi control signal.eBoost™ Operation Mode and IEMi OperationMode will be temporarily inhibited.4609 eBoost INHIBITED - LOW LOAD eBoost™ Operation Mode inhibited due to minimalload not reached.4699 BATTERY TEST IMPOSSIBLEAutomatic Battery Test is not possible due to:- No Mains Rectifier or Bypass.- Battery not fully charged.- Load is below 10% or above 80%.Test is postponed for 1 week.4763 REMOTE CONTROL ONInverter can be started or shut-down by remotecontrol.Commands source can be chosen depending onthe value of parameter (Service only):0 = Only local panel1 = Only Remote Control2 = Both4764 REMOTE CONTROL OFFInverter cannot be started or shut-down by remotecontrol.Commands source can be chosen depending onthe value of parameter (Service only):0 = Only local panel1 = Only Remote Control2 = Both4798 SERVICE KEY ACTIVATED A valid Service Key has been entered.It will no longer be requested in the next 6 hours.4799 SERVICE KEY DEACTIVATED The Service Key validity period has expired.