Critical PowerModifications reserved Page 104/146GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx User Manual TLE Series 600 & 800 CE S1During the first commissioning TLE Series 600 & 800 requests a set-up of the UPS configurationparameters presented in the following “Power-Up” screen.Without such configuration it is not possible to continue with the commissioning procedure.WARNING !The set-up of the UPS configuration parameters must be done only by QUALIFIEDAND TRAINED PERSONNEL.The set-up of mistaken values could compromise the integrity and reliability of theUPS.UPSLanguage This parameter allows the choice of language used to display theinformation.Date (dd.mm.yyyy) You can adjust the date of the real time clock existing in the UPS by themeans of this parameter.The value you enter is thoroughly checked to be a correct date in theformat “dd.mm.yyyy”.Time (24h) You can adjust the time of the real time clock existing in the UPS bymeans of this parameter.The value you enter is thoroughly checked to be a correct time in theformat “hh.mm.ss”.The time is specified in 24-hour format.Input Frequency Input frequency value (50 Hz / 60Hz).Output Frequency Inverter output frequency value (50 Hz / 60Hz).Inverter Voltage Output voltage PHASE/NEUTRAL of the inverter (220V / 230V / 240V).Continue ►