Critical PowerModifications reserved Page 61/146GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx User Manual TLE Series 600 & 800 CE S15.9.5 Use of TLE Series 600 & 800 in eBoost™ Operation ModeNOTE !For systems intended to be operated in eBoost™ Operation Mode, the installationshall be protected with suitable surge protection devices (SPDs) on the AC busfeeding the UPSs.Please contact your Service Centre for more information.NOTE !In eBoostTM Operation Mode the inverter output filter is placed in parallel with theload, and combined with the load current it contributes to the UPS inputcharacteristic.As the inverter output filter exhibits a predominantly capacitive characteristic, itmay provide some degree of reactive power compensation when combined withlagging power factor loads.Conversely, depending on the load type and level, the UPS input characteristicmay exhibit a leading power factor in eBoostTM Operation Mode.Please contact your Service Centre for more information.NOTE !If an emergency generator set supplies the UPS in case of Mains Failure, and thesystem is intended to be operated in eBoost™ Operation Mode, eBoost operationshall be prevented during generator operation.This can be accomplished by either installing a “GENERATOR ON” signal (refer toSection 9.2.5) or an “eBoost/IEMi CONTROL” signal (refer to Section 9.2.7).Please contact your Service Centre for more information.