Critical PowerModifications reserved Page 97/146GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx User Manual TLE Series 600 & 800 CE S1COMMANDS 1 SCREENAllows the user to execute UPSoperation commands.RectifierRectifier ONRectifier switching ON command.Rectifier RESETRectifier restore command.Reserved for the Service Centre.Led Rectifier statusIndicates the Rectifier’s status: ON = lit OFF = turned OffInverterInverter ONInverter switching ON command.NOTE !When eBoost™ Operation Mode or IEMi Operation Mode is enabled, control ofInverter status and selection of the feed path is done autonomously by theUPS control logic.Therefore, Inverter ON / Inverter OFF commands are disabled when eBoost™Operation Mode or IEMi Operation Mode is enabled.Inverter OFFInverter switching OFF command.This command is also used as EPO (Emergency Power Off) reset after the contact closing.NOTE !Inverter OFF command is disabled when eBoost™ Operation Mode or IEMiOperation Mode is enabled.Led inverter statusIt indicates the Inverter status:ON / OFF / Pre-charge / Pre-charge completed / Soft-start