Critical PowerModifications reserved Page 57/146GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx User Manual TLE Series 600 & 800 CE S1NOTE !To meet standards concerning electromagnetic compliance, the connectionbetween the UPS and external Battery must be done by using a shielded cable orsuitable shielded (steel) conduit!This UPS is only designed to operate in a wye-configured electrical system with asolidly grounded neutral.If the UPS is equipped with an input bypass transformer, the secondary of thetransformer must be wye-configured with neutral solidly grounded.Installation notices in case of power connection with Separate Mains InputFig. 5.9.2-2 TLE Series 600 - Interconnection links BR1, BR2 and BR3NOTE !For separate Bypass and Rectifier input configuration, the interconnection linksBR1, BR2 and BR3 MUST BE REMOVED (see Fig. 5.9.2-2).INTERCONNECTIONS LINKSBR1, BR2 and BR3MUST BE REMOVED!1RectifierMainsBR32BypassMainsBR2BR1LoadL3LoadL2LoadL1BR3BR2BR1L2-2L3-2NMains NeutralLoad NeutralNMains NeutralLoad NeutralL2-1L3-1L1-2L1-1Q1A