11.9 F: Options362 YASKAWA SIEPC71061753A GA500 Technical ManualNo.(Hex.) Name Description Default(Range) Ref.F1-11(038A)Speed Deviation DetectDelayTime Sets the length of time that the difference between the frequency reference and speedfeedback must be more than the level in F1-10 to cause dEv [Speed Deviation].Note:When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RPPulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.0.5 s(0.0 - 10.0 s)578F1-14(038D)Encoder Open-CircuitDetect Time Sets the length of time that the drive must not receive a pulse signal to cause PGo[Encoder (PG) Feedback Loss].Note:Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent]faults.When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RPPulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.2.0 s(0.0 - 10.0 s)578◆ F6: Communication OptionsNo.(Hex.) Name Description Default(Range) Ref.F6-01(03A2)Communication ErrorSelection Sets the method to stop the motor or let the motor continue operating when the drivedetects bUS [Option Communication Error].0 : Ramp to Stop1 : Coast to Stop2 : Fast Stop (Use C1-09)3 : Alarm Only4 : Alarm (Run at d1-04)5 : Alarm - Ramp Stop1(0 - 5)584F6-02(03A3)Comm External Fault(EF0) Detect Sets the conditions at which EF0 [Option Card External Fault] is detected.0 : Always Detected1 : Detected during RUN Only0(0, 1)584F6-03(03A4)Comm External Fault(EF0) Select Sets the method to stop the motor or let the motor continue operating when the drivedetects EF0 [Option Card External Fault].0 : Ramp to Stop1 : Coast to Stop2 : Fast Stop (Use C1-09)3 : Alarm Only1(0 - 3)584F6-04(03A5)bUS Error DetectionTime Sets the delay time for the drive to detect bUS [Option Communication Error].Note:When you install an option card in the drive, the parameter value changes to 0.0 s.2.0 s(0.0 - 12.0 s)585F6-06(03A7)Torque Reference/Limitby Comm Sets the function that enables and disables the torque reference and torque limitreceived from the communication option.0 : Disabled1 : Enabled0(0, 1)585F6-07(03A8)Multi-Step Ref @NetRef/ComRef Sets the function that enables and disables the multi-step speed reference when thefreqency reference source is NetRef or ComRef (communication option card orMEMOBUS/Modbus communications).0 : Disable Multi-Step References1 : Enable Multi-Step References1(0, 1)585F6-08(036A)Comm Parameter Reset@Initialize Sets the function to initialize F6-xx and F7-xx parameters when the drive is initializedwith A1-03 [Initialize Parameters].0 : No Reset - Parameters Retained1 : Reset Back to Factory Default0(0, 1)585F6-10(03B6)CC-Link Node AddressSets the node address for CC-Link communication. Restart the drive after you changethe parameter setting.Note:Be sure to set a node address that is different than all other node addresses. Do notset this parameter to 0. Incorrect parameter settings will cause AEr [Station AddressSetting Error] errors and the L.ERR LED on the option will come on.0(0 - 64)585V/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLV