Parameter List1111.11 L: Protection FunctionsYASKAWA SIEPC71061753A GA500 Technical Manual 391No.(Hex.) Name Description Default(Range) Ref.L5-07(0B2A)Fault Reset EnableSelect Grp1 Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, thedigits set oL1, oL2, oL3, and oL4, in order.0000 : Disabled0001 : Enabled (—/—/—/oL4)0010 : Enabled (—/—/oL3/—)0011 : Enabled (—/—/oL3/oL4)0100 : Enabled (—/oL2/—/—)0101 : Enabled (—/oL2/—/oL4)0110 : Enabled (—/oL2/oL3/—)0111 : Enabled (—/oL2/oL3/oL4)1000 : Enabled (oL1/—/—/—)1001 : Enabled (oL1/—/—/oL4)1010 : Enabled (oL1/—/oL3/—)1011 : Enabled (oL1/—/oL3/oL4)1100 : Enabled (oL1/oL2/—/—)1101 : Enabled (oL1/oL2/—/oL4)1110 : Enabled (oL1/oL2/oL3/—)1111 : Enabled (oL1/oL2/oL3/oL4)1111(0000 - 1111)693L5-08(0B2B)Fault Reset EnableSelect Grp2 Use these 4 digits to set the Auto Restart function for Uv1, ov, oH1, and GF. From leftto right, the digits set Uv1, ov, oH1, and GF, in order.0000 : Disabled0001 : Enabled (—/–/—/GF)0010 : Enabled (—/–/oH1/–)0011 : Enabled (—/–/oH1/GF)0100 : Enabled (—/ov/—/–)0101 : Enabled (—/ov/—/GF)0110 : Enabled (—/ov/oH1/–)0111 : Enabled (—/ov/oH1/GF)1000 : Enabled (Uv1/–/—/–)1001 : Enabled (Uv1/–/—/GF)1010 : Enabled (Uv1/–/oH1/–)1011 : Enabled (Uv1/–/oH1/GF)1100 : Enabled (Uv1/ov/—/–)1101 : Enabled (Uv1/ov/—/GF)1110 : Enabled (Uv1/ov/oH1/–)1111 : Enabled (Uv1/ov/oH1/GF)1111(0000 - 1111)694◆ L6: Torque DetectionNo.(Hex.) Name Description Default(Range) Ref.L6-01(04A1)Torque DetectionSelection 1 Sets the speed range that detects overtorque and undertorque and the operation of drives(operation status) after detection.0 : Disabled1 : oL @ Speed Agree - Alarm only2 : oL @ RUN - Alarm only3 : oL @ Speed Agree - Fault4 : oL @ RUN - Fault5 : UL @ Speed Agree - Alarm only6 : UL @ RUN - Alarm only7 : UL @ Speed Agree - Fault8 : UL @ RUN - Fault0(0 - 8)696L6-02(04A2)Torque Detection Level1 Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, driverated output current = 100% value. In vector control, motor rated torque = 100% value.150%(0 - 300%)697L6-03(04A3)Torque Detection Time 1Sets the detection time for Overtorque/Undertorque Detection 1.0.1 s(0.0 - 10.0 s)697V/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLV