Parameter List1111.17 U: MonitorsYASKAWA SIEPC71061753A GA500 Technical Manual 41311.17 U: Monitors◆ U1: Operation Status MonitorsNo.(Hex.) Name Description MFAO Signal LevelU1-01(0040)Frequency referenceShows the actual frequency reference value. Parameter o1-03 [Keypad Display Unit Selection]sets the display units.Unit: 0.01 Hz10 V = Maximumfrequency (-10 V to +10 V)U1-02(0041)Output FrequencyShows the actual output frequency. Parameter o1-03 [Keypad Display Unit Selection] sets thedisplay units.Unit: 0.01 Hz10 V = Maximumfrequency (-10 V to +10 V)U1-03(0042)Output CurrentShows the actual output current.The keypad shows the value of U1-03 in amperes (A). When looking at the monitor throughMEMOBUS/Modbus communications, the current is “8192 = drive rated current (A)”. Calculatethe current from the monitor value that is in at MEMOBUS/Modbus communications using“Numerals being displayed / 8192 × drive rated current (A).Unit: When the drive model changes, the display units for this parameter also change.• 0.01 A units: 2001 to 2042, B001 to B018, 4001 to 4023• 0.1A units: 2056 to 2082, 4031 to 406010 V = Drive rated currentU1-04(0043)Control method selectionShows the drive control method.0 : V/f Control2 : Open Loop Vector5 : PM Open Loop Vector6 : PM Advanced Open Loop Vector8 : EZ Vector ControlNo signal output availableU1-05(0044)Motor SpeedShows the actual detected motor speed. Parameter o1-03 [Keypad Display Unit Selection] sets thedisplay units.Unit: 0.01 Hz10 V = Maximumfrequency (-10 V to +10 V)U1-06(0045)Output Voltage RefShows the output voltage reference.Unit: 0.1 V200 V class: 10 V = 200Vrms400 V class: 10 V = 400VrmsU1-07(0046)DC Bus VoltageShows the DC bus voltage.Unit: 1 V200 V class: 10 V = 400 V400 V class: 10 V = 800 VU1-08(0047)Output PowerShows the internally-calculated output power.Changing the setting of A1-02 [Control Method Selection] also changes the signal level of theanalog output.• A1-02 = 0: Drive capacity (kW)• A1-02 = 2: Motor Rated Power [E2-11] (kW)• A1-02 = 5, 6: PM Motor Rated Power [E5-02] (kW)• A1-02 = 8: Motor Rated Power [E9-07] (kW)Unit: When the drive model changes, the display units for this parameter also change.• 0.01 A units: 2001 to 2042, B001 to B018, 4001 to 4023• 0.1A units: 2056 to 2082, 4031 to 406010 V: Drive capacity (motorrated power) kW(-10 V to +10 V)U1-09(0048)Torque ReferenceShows the internal torque reference value.Unit: 0.1%10 V = Motor rated torque(-10 V to +10 V)U1-10(0049)Input Terminal StatusShows the status of the MFDO terminal where = ON and = OFF.For example, U1-10 shows when terminals S1 and S3 are ON.bit0 : Terminal S1 (MFDI 1)bit1 : Terminal S2 (MFDI 2)bit2 : Terminal S3 (MFDI 3)bit3 : Terminal S4 (MFDI 4)bit4 : Terminal S5 (MFDI 5)bit5 : Terminal S6 (MFDI 6)bit6 : Terminal S7 (MFDI 7)bit7 : Not used (normal value of [ ]).No signal output availableV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLV