12.11 o: Keypad-Related Settings736 YASKAWA SIEPC71061753A GA500 Technical Manual■ o1-51: Trend Plot Time Scale SettingNo.(Hex.) Name Description Default(Range)o1-51(11CB)RUNTrend Plot Time ScaleSetting Sets the time scale (horizontal axis) to display the trend plot. When you change this setting, thedrive automatically adjusts the data sampling time. This parameter is only available when usingan LCD keypad.300 s(1 - 3600 s)■ o1-55: Analog Gauge Area SelectionNo.(Hex.) Name Description Default(Range)o1-55(11EE)RUNAnalog Gauge AreaSelection Sets the range used to display the monitor set in o1-24 [Custom Monitor 1] as an analog gauge.This parameter is only available when using an LCD keypad.1(0, 1)0 : +/- Area ( - o1-56 ~ o1-56 )1 : + Area ( 0 ~ o1-56 )■ o1-56: Analog Gauge Area SettingNo.(Hex.) Name Description Default(Range)o1-56(11EF)RUNAnalog Gauge Area SettingSets the value used to display the monitor set in o1-24 [Custom Monitor 1] as an analog meter.This parameter is only available when using an LCD keypad.100.0%(0.0 - 100.0%)■ o1-58: Motor Power Unit SelectionNo.(Hex.) Name Description Default(Range)o1-58(3125)Motor Power Unit SelectionSets the setting unit for parameters that set the motor rated power.0(0, 1)The drive shows these parameter values in the set units:• E2-11 [Motor Rated Power]• E4-11 [Motor 2 Rated Power]• E5-02 [PM Motor Rated Power]• E9-07 [Motor Rated Power]• T1-02 [Motor Rated Power]• T2-04 [PM Motor Rated Power]• T4-08 [Motor Rated Capacity]0 : kWShows the motor output in kW units.1 : HPShows the motor output in HP units.◆ o2: Keypad Operation■ o2-01: LO/RE Key Function SelectionNo.(Hex.) Name Description Default(Range)o2-01(0505)LO/RE Key FunctionSelectionSets the function that lets you use to switch between LOCAL and REMOTE Modes.1(0, 1)0 : DisabledYou cannot use to switch between LOCAL and REMOTE Modes.1 : EnabledV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLVV/f OLV OLV/PMOLV/PM AOLV/PM EZOLV