11.21 Defaults by Drive Model and Duty Rating ND/HD436 YASKAWA SIEPC71061753A GA500 Technical ManualNo. *1 Name Unit Default- Drive Model - 2070 2082C6-01 Normal / HeavyDuty Selection -HD ND HD ND0 1 0 1o2-04 Drive Model (KVA)Selection Hex. 6E 6FE2-11(E4-11, E5-02) Motor Rated Power kW 15 18.5 18.5 22L2-04 Powerloss V/fRecovery Ramp Time s 0.6 0.6 0.6 0.6L2-05 Undervoltage DetectionLvl (Uv1) - 190 190 190 190L3-02 Stall Prevent Levelduring Accel % 150 120 150 120L3-06 Stall Prevent Levelduring Run % 150 120 150 120L3-24 Motor Accel Time @Rated Torque s 0.244 0.317 0.317 0.355L8-02 Overheat Alarm Level °C 120 120 135 135L8-09 Output Ground FaultDetection - 1 1 1 1n1-03 Hunting PreventionTime Constant ms 10 10 10 10n3-02 HSB Current LimitLevel % 150 120 150 120n5-02 Motor InertiaAcceleration Time s 0.244 0.317 0.317 0.355*1 Parameters within parentheses are for motor 2.◆ Single-Phase 200 V ClassNo. *1 Name Unit Default- Drive Model - B001 B002 B004 B006C6-01Normal /Heavy DutySelection -HD ND HD ND HD ND HD ND0 1 0 1 0 1 0 1o2-04Drive Model(KVA)Selection Hex. 30 31 32 33E2-11(E4-11, E5-02)Motor RatedPower kW 0.1 0.2 0.2 0.4 0.4 0.75 0.75 1.1b3-04V/f Gainduring SpeedSearch % 100 100 100 100 100 100 100 100b3-06SpeedEstimationCurrent Level1- 1 1 1 1 1 1 0.5 0.5b3-08SpeedEstimationACR P Gain - 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5b3-26DirectionDeterminationLevel - 1000 1000 1000 1000 1000 1000 1000 1000b8-03 Energy SavingFilter Time s 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5b8-04 Energy SavingCoefficientValue- 481.7 356.9 356.9 288.2 288.2 223.7 223.7 196.6C6-02 CarrierFrequencySelection- 4 7 4 7 4 7 4 7E2-01(E4-01)Motor RatedCurrent (FLA) A 0.6 1.1 1.1 1.9 1.9 3.3 3.3 6.2E2-02(E4-02)Motor RatedSlip Hz 2.5 2.6 2.6 2.9 2.9 2.5 2.5 2.6