7 Utility Functions (Fn)7-127.6 Initializing Parameter Settings (Fn005)This function is used when returning to the factory settings after changing parameter settings.Note: Any value adjusted with Fn009, Fn00A, Fn00B, Fn00C, Fn00D, Fn00E, and Fn00F cannot be initialized by Fn005.(1) PreparationThe following conditions must be met to initialize the parameter values.• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).• The servo ON signal (/S-ON) must be OFF.(2) Operating ProcedureUse the following procedure.• Be sure to initialize the parameter settings while the servo ON (/S-ON) signal is OFF.• After initialization, always turn the control power supply OFF and ON again to validatethe settings.Step Display afterOperation Keys Operation1 Press the MODE/SET Key to select the utility function.2 Press the UP or DOWN Key to select Fn005.3 Press the DATA/SHIFT Key for approximately one second.The display shown on the left appears.4Press the MODE/SET Key. Then, the parameters will beinitialized.When the initialization has been completed, "donE" flasheson the display and returns to the screen as shown on the left.5 When you finish initializing the parameter settings, turn the control power supply OFF and ON again.MODE/SET DATA /MODE/SET DATA/MODE/SET DATA/MODE/SET DATA /