7 Utility Functions (Fn)7-247.15 Resetting Configuration Error of Option Module (Fn014)The SERVOPACK with option module recognizes installation status and types of option module which is con-nected to SERVOPACK. If an error is detected, the SERVOPACK issues an alarm.This function resets these alarms.For alarm types and corrective actions, refer to 10 Troubleshooting.Note 1. Alarms related to option module can be cleared only by this function. These alarms cannot be cleared by alarmreset or turning OFF the main circuit power supply.2. Before clearing the alarm, perform corrective action for the alarm.(1) Operating ProcedureFollow the steps below.Step Display afterOperation Keys Operation1 Press the MODE/SET Key to select the utility functionmode.2Press the UP or DOWN Key to select Fn014.Note: When "no-oP" blinks for approximately one second,the write prohibited setting is set in Fn010. Changethe setting in Fn010, and press the key again afterenabling writing. (Refer to 7.12.)3 Press the DATA/SHIFT Key for approximately one second.The display shown on the left appears.4 Press the UP or DOWN Key to select option module to becleared.5 Press the MODE/SET Key for approximately one second.The display shown on the left appears.6 Display blinks↓Press the MODE/SET Key again. The display changes asshown on the left and the configuration error of option mod-ule is cleared.7 The display changes from "done" to the display shown onthe left.8 Press the DATA/SHIFT Key for approximately one second."Fn014" is displayed again.9 Turn OFF the power and then turn ON again to validate the setting.MODE /SET DATA /MODE/SET DATA/MODE/SET DATA/MODE/SET DATA/MODE /SET DATA /MODE /SET DATA /MODE/SET DATA/