Specifications Product DescriptionUnimode 9600 PN 51336:C 11/06/01 15EIA-485 (ACS) - TB6ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-)EIA-485 (TERM) - TB7Terminal Mode annunciator connector, Terminal 5 (In +), 6 (In -), 7 (Out +), 8 (Out -)EIA-232 (ACS) - TB7PC/Printer Connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground)Auxiliary Trouble Inputs - J16 & J17Two-pin connectors which can be used to monitor trouble conditions on auxiliaryequipment. They can be connected to the trouble bus of a peripheral such as the ADT-CHG-120 or to the normally-open dry contacts of a trouble relay.CAUTION! Do not connect power to these connectors since circuit damage may result.1.3.1 Current AvailabilityThe following figure illustrates the maximum current that is possible for each panel circuitand the total current available from the FACP power supply.3 amps maxper circuit3 amps maxper circuit3 amps maxper circuit3 amps maxper circuit3 amps maxper circuitResettable Powerfor 4-WireSmoke DetectorsNonresettablePower # 1NonresettablePower # 2NAC # 1NAC # 2Standby6 amps maxper panelAlarm7 amps maxper panel12345678123456TB4TB3Figure 1.1 Current AvailabilityRefer to the battery calculations section for additional information.