Master Programming Level ProgrammingUnimode 9600 PN 51336:C 11/06/01 733.6.2.7 Zone TypeZone Types must be programmed only if a DACT, programmed for zone reporting, isinstalled on the control panel. Pressing 1 for Zone Types, while viewing Zone SetupScreen #3, will display a screen similar to the following:This display will show the system zones (default and user programmed) and theirassociated types. Note that an up and/or down arrow will appear in the upper rightcorner of the display, indicating that additional screens of zone information exists.Press the up or down arrow keys to view zones Z00 through Z99.Zone types can be changed by pressing the keypad number key corresponding to thezone in each Zones Installed Screen. Available zone types will be displayed in theresultant screens. For example, to change the zone type for zone Z02 in the screenillustrated above, press 3. The following screens will be displayed:To change the zone type for Z02 to Pull Station, scroll the display until Zone TypeProgram Screen #2 is displayed. Press 2 to program zone Z02 as a Pull Station zone.The display will return to the Zones Installed Screen showing zone Z02 and the PullStation program type. Repeat the procedure for each zone to be changed.IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assigna Waterflow silenceable zone type to the selected zone. Any signaling devicesprogrammed to the same zone can be silenced by pressing the Alarm Silence key or byusing the auto-silence feature.To program a waterflow circuit as nonsilenceable, connect the waterflow device(s) to amonitor module programmed as a Waterflow device (see "Edit Module Screen forMonitor Module" on page 54) and assign the module to a particular zone. Program acontrol module as nonsilenceable (see "Edit Module Screen for Control Modules" onpage 63) and assign it to the same zone as the waterflow type monitor module. Allnotification appliances connected to the control module will be nonsilenceable as willany other devices assigned to the same zone.ZONE SETUP1=ZONE TYPESZone Setup Screen #3@@ZONE@TYPE@PROG1=Z00@@ALARM2=Z01@@ALARM3=Z02@@ALARMZones Installed Screen@@ZONE@TYPE@PROG1=ALARM2=SMOKE3=WATERFLOWZone Type Program Screen #1@@ZONE@TYPE@PROG1=MEDICAL2=HAZARD3=TAMPERZone Type Program Screen #3@@ZONE@TYPE@PROG1=SUPERVISORY2=PROC.@MON3=VOICE@EVACZone Type Program Screen #4@@ZONE@TYPE@PROG1=HEAT2=PULL@STATION3=DUCTZone Type Program Screen #2