- - *$$ , 3.6.8 WalktestWalktest allows an individual to test the fire alarm system without the necessity to resetthe control panel after each device activation. Pressing 2 while viewing the ProgrammingScreen #3 will cause the following Walktest options to be displayed:To perform a silent walktest which will not sound the NACs, press 1 while viewing theWalktest Screen. To perform an audible walktest, which will sound the NACs, press 2while viewing the Walktest Screen. When either option is chosen, the panel will enterWalktest Mode and the following screen will be displayed:The user can now perform a one-person walktest by activating devices throughout thesystem. As each device is activated, the screen will display the information about theactivated device as shown below. Note that the colon in the time is replaced with anasterisk to distinguish the walktest screen from an actual alarm screen.After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode andreturn to the Walktest Screen. The results of the Walktest can now be viewed by pressing3 while viewing the Walktest Screen. The following screen will be displayed:Use the up and down arrow keys to view all of the walktest results which will be displayedas illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If allpower (AC and DC) is removed from the FACP, the Walktest log information will be lost.This information is also overwritten when subsequent walktests are performed.PROGRAMMING1=HISTORY2=WALKTEST3=OPTION MODULESProgramming Screen #3@@@@@WALKTEST1=SILENT2=AUDIBLE3=VIEW@RESULTWalktest Screen@UNIT@IN@WALKTESTWalktest Active ScreenALARM@@PULL@STATION@@@@@@@@@@@@@@@@@@@@@Z000@10*00A@010801@1M001@@WALKTEST@RESULTSView Result Screen