EATON BladeUPS® (12 kVA) User's Guide 164201649 Rev 4www.eaton.com/powerquality 99Chapter 7 SpecificationsThis chapter provides the following specifications: Model list Weights and dimensions Electrical input and output Environmental and safety BatteryTable 9. Model ListUPS Model Number Power Levels(Rated at Nominal Inputs)BladeUPS 12 module 12 kVA or 12 kW at 208V*BladeUPS 12i module 12 kVA or 12 kW at 400V*EBM Model NumberBladeEBMBladeUPS Bar Model NumberBladeUPS Bar 60 For up to 6 UPSs* Derated for line cord and nominal line voltageCord Model Number Description Input Plug Type LengthUPSCord12UL 12 kW UL input IEC 309-60A 3.7m (12 ft)UPSCord12ULR 12 kW UL input/output IEC 309-60A 1.8/1.2m (6/4 ft)UPSCordPUL 12 kW UL parallel Anderson* 0.5m (1.5 ft)UPSCord12CE 12 kW CE input IEC 309-32A 3.7m (12 ft)UPSCord12CER 12 kW CE input/output IEC 309-32A 1.2/1.2m (4/4 ft)UPSCord12PCE 12 kW CE parallel Anderson* 0.5m (1.5 ft)* Customized Anderson connector for use with Eaton BladeUPS BarTable 10. Weights and DimensionsUPS Extended Battery Module (EBM)Dimensions (WxDxH) 441 x 660 x 261 mm17.4” x 26” x 10.3” (6U)438 x 660 x 131 mm17.2” x 26.0” x 5.2” (3U)Weights BladeUPS 12 module without internal batteries: 61 kg (135 lb)BladeUPS 12i module without internal batteries: 63.5 kg (140 lb)BladeUPS 12 module with internal batteries: 141 kg (311 lb)BladeUPS 12i module with internal batteries: 143 kg (316 lb)Individual battery: 2 kg (4.4 lb)Each battery tray: 20 kg (44 lb)BladeUPS 12 electronics module: 19.5 kg (43 lb)BladeUPS 12i electronics module: 21.8 kg (48 lb)77 kg (170 lb)