COMMUNICATIONEATON BladeUPS® (12 kVA) User's Guide 164201649 Rev 4www.eaton.com/powerquality80X-Slot CardsX-Slot cards allow the UPS to communicate in a variety of networking environmentsand with different types of devices. The BladeUPS has two available communicationbays for any X-Slot card, including: ConnectUPS-X Web/SNMP Card - has SNMP and HTTP capabilities as well asmonitoring through a Web browser interface; connects to a twisted-pair Ethernet(10/100BaseT) network. It has a built-in switching hub that allows three additionalnetwork devices to be connected to the network without the requirement ofadditional network drops. In addition, you can attach an Eaton EnvironmentalMonitoring Probe to obtain humidity, temperature, smoke alarm, and securityinformation. Relay Interface Card - has isolated dry contact (Form-C) relay outputs for UPS status:Utility failure, Low battery, UPS alarm/OK, or On bypass. Modbus ® Card - allows you to continuously and reliably monitor the UPSs in yourBuilding Management System (BMS). Industrial Relay Card (IRC) - is used to indicate the operating status of the UPSsystem using the customer's monitoring equipment. The IRC uses four isolatednormally-open or normally-closed dry relay contacts to indicate the UPS status. Youcan monitor Normal, Bypass, Battery, and Alarm mode. Modem Card - provides out-of-band remote notification and monitoring usingmodem communication directly to cell phones and pagers.See Figure 46 on page 77 for the location of the two X-Slot communication bays.Relay Interface CardModbus CardModem CardConnectUPS-X Web/SNMP Card Industrial Relay CardFigure 49. Optional X-Slot Cards