OPERATIONEATON BladeUPS® (12 kVA) User's Guide 164201649 Rev 4www.eaton.com/powerquality66User SettingsThe following table displays the options that you can change.Table 4. User SettingsDescription Available Settings Default SettingSet Date and Time Set Year, Month, DayDate: mm/dd/yyyySet Hours, MinutesTime is a 24-hour clock.01/01/200300:00Display Contrast Adjust contrast with up/down arrow buttons. ModerateChange Language Select LanguageAvailable languages depend on model and languages installed.EnglishRelay Config Relay: [Alarm-1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4]Setup: [On Battery] [Summary Alarm] [On Bypass] [UPS OK][custom] [empty]Alarm 1: emptyX-Slots (1 or 2)#1: UPS OK#2: On Bypass#3: Summary Alarm#4: On BatterySignal Inputs Signal: [X-Slot-1] [X-Slot-2] [INPUT 1] [INPUT 2][signal inputs]Logic: [0] [1]For more information, see “Programmable Signal Inputs” onpage 82.[1]Serial Port Config Port: [X-Slot-1] [X-Slot-2/Serv]Speed: [19200] [9600] [2400] [1200]19200Parallel Operation Settings Parallel Operation Mode:[Redundant Mode] [Capacity Mode]This setting is not available for six-unit systems (must be RedundantMode only).Redundant ModeParallel XCP: [System] [Sub Unit]Select Sub Unit for PowerVision software. Select System forother software.SystemAuto ID Restart: [Done] [Restart]Select Restart to reinitialize auto identification (see“Auto-Identification” on page 87).NoneModem Config Modem Installation: [Not Installed] [X-Slot-1] [X-Slot-2] Not InstalledSet Modem Call Events Event #0Call modem: noSet Modem Init String ATZ0Set Modem Call Command NoneSet Modem Communication Password None