OPERATIONEATON BladeUPS® (12 kVA) User's Guide 164201649 Rev 4www.eaton.com/powerquality7210. Press any button on the front panel display to activate the menu options. SelectCONTROL and GO TO BYPASS MODE.The indicator illuminates solid and the indicator flashes, indicating theUPS is operating in Bypass mode. The load is now powered by utility power.If the indicator is flashing, do not proceed until all alarms are clear. Check theUPS status from the front panel to view the active alarms. Correct the alarms andrestart if necessary.11. Switch the load connector circuit breaker to the ON () position.12. Press the ESC button until the Start screen appears.Standalone UPS ShutdownTo shut down a standalone UPS (see Figure 32 on page 43):1. Switch the load connector circuit breaker to the OFF (O) position.NOTE The load connector breaker controls the load connector only, not the output power cord.2. Press any button on the front panel display to activate the menu options. SelectTURN UPS ON/OFF, TURN UPS OFF, and press the button.3. Confirm the selection. Press and hold the button for three seconds, until theUPS stops beeping.The output relays open, the UPS transfers to Standby mode, and theindicator turns off.4. Switch the UPS battery circuit breaker to the OFF (O) position.5. If optional EBMs are installed, switch all EBM battery circuit breakers to theOFF (O) position.6. Switch the UPS input circuit breaker to the OFF (O) position.7. Switch off utility power where the UPS is connected.Individual Paralleled UPS ShutdownTo shut down an individual UPS in the parallel system (see Figure 32 on page 43):1. Switch the load connector circuit breaker to the OFF (O) position.NOTE The load connector breaker controls the load connector only, not the output power cord.2. Press any button on the front panel display to activate the menu options. SelectTURN UPS ON/OFF, TURN UPS OFF, and press the button.3. Confirm the selection. Press and hold the button for three seconds, until theUPS stops beeping.The output relays open, the UPS transfers to Standby mode, and theindicator turns off.4. Switch the UPS battery circuit breaker to the OFF (O) position.