OPERATIONEATON BladeUPS® (12 kVA) User's Guide 164201649 Rev 4www.eaton.com/powerquality 7112. Confirm the selection. Press and hold the button for three seconds, until theUPS stops beeping.Verify that the indicator illuminates solid on each UPS, indicating that theUPS is operating normally and any loads not connected through the LoadConnector are now energized.If the indicator on any UPS is flashing, do not proceed until all alarms areclear. Check the UPS status from the front panel to view the active alarms.Correct the alarms and restart if necessary.Each UPS should be in Normal mode. By default, Normal mode operates on theHigh Efficiency setting (see “Normal Mode” on page 67).13. To energize loads connected through the Load Connectors, switch all loadconnector circuit breakers to the ON () position.14. On any UPS, press the ESC button until the Start screen appears.Starting the UPS on Internal BypassNOTE Starting the UPS on internal bypass leaves the load unprotected.To start a standalone UPS on internal bypass (see Figure 32 on page 43):1. Verify that all UPS circuit breakers are in the OFF (O) position.NOTE The load connector breaker controls the load connector only, not the output power cord.2. Verify that the UPS power cord is plugged in.3. Switch on utility power where the UPS is connected.4. Switch the UPS input circuit breaker to the ON () position.5. Wait for the UPS front panel display to illuminate.The indicator flashes on the UPS.6. Check the UPS front panel display for active alarms or notices (other than“Batteries Disconnected”). Resolve any active alarms before continuing. See“Troubleshooting” on page 105.7. Switch the UPS battery circuit breaker to the ON () position.8. If optional EBMs are installed, switch all EBM battery circuit breakers to theON () position.9. Verify that the “Batteries Disconnected” alarm has cleared. Verify that no otheralarms appear on the UPS front panel display.If the indicator is flashing, do not proceed until all alarms are clear. Check theUPS status from the front panel to view the active alarms. Correct the alarms andrestart if necessary.