INSTALLATIONEATON BladeUPS® (12 kVA) User's Guide 164201649 Rev 4www.eaton.com/powerquality 59Standalone UPS Initial StartupTo start up a standalone UPS:NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.1. Plug the equipment to be protected into the UPS, but do not turn on theprotected equipment (see Figure 32 on page 43).2. Make any necessary provisions for cord retention and strain relief.3. Verify that all UPS circuit breakers are in the OFF (O) position.NOTE The load connector breaker controls the load connector only, not the output power cord.4. Verify that the UPS power cord is plugged in.5. Switch on utility power where the UPS is connected.6. Remove the breaker ties from the circuit breakers.7. Switch the UPS input circuit breaker to the ON () position.8. Wait for the UPS front panel display to illuminate.The indicator flashes on the UPS.9. Check the UPS front panel display for active alarms or notices (other than“Batteries Disconnected”). Resolve any active alarms before continuing. See“Troubleshooting” on page 105.10. Switch the UPS battery circuit breaker to the ON () position.11. If optional EBMs are installed, switch all EBM battery circuit breakers to theON () position.12. Verify that the “Batteries Disconnected” alarm has cleared. Verify that no otheralarms appear on the UPS front panel display.If the indicator is flashing, do not proceed until all alarms are clear. Check theUPS status from the front panel to view the active alarms. Correct the alarms andrestart if necessary.13. Press any button on the front panel display to activate the menu options, andthen press the button until the TURN UPS ON/OFF menu displays.14. Press the button to display the TURN UPS ON option; press the button.