Programming theEU5C-SWD-CAN11803/11 MN05013002Z-ENModule CFG (0x2102)• Content– Subindex = 0:The subindex 0 represents the number of SmartWire-DTslaves registered in the target configuration.– Subindex = 1 to the number of SmartWire-DT slaves:Number and format of the input and output data madeavailable to these slaves• Read accessData are returned from the stored gateway target configura-tion.• Write accessData are written to the Planned configuration. Thewriting may be performed only in “pre-operational” status.The module must support the changed configurationsettings.Module serial number (0x2103)• Content– Subindex = 0:The subindex 0 represents the number of SmartWire-DTslaves registered in the target configuration.– Subindex = 1 to the number of SmartWire-DT slaves:Serial number of the slave found in the correspondingplace• Read accessData are returned from the target configuration. (storedgateway target configuration)• Write accessNot permissible.