Diagnostics6703/11 MN05013002Z-ENExtended diagnosis (module related)The extended diagnostics contain the slave address of theSmartWire-DT slave, status information and one or severaldetailed specifications relating to error or diagnostic causes.You can find the meaning of the specifications in the manualMN05006001Z-EN (previously AWB2723-1613en).Table 7: Structure of the extended diagnosis2-bitstatuscodeExplanation00 A cyclic data interchange is performed with therespective SmartWire-DT slave.01 A diagnostic message from the SmartWire-DTslave is pending.10 Configuration error (incompatible SmartWire-DTslave.)11 Failure of a SmartWire-DT slaveByte Value Description1 Ly Length of detailed status message2 0xA1 Status type3 SmartWire-DT slave address (1 - 58)4 0 -5 first detailed diagnostic message/statusmessage6 -Ly nth detailed diagnostic message/statusmessage