Putting the SmartWire-DTnetwork into operation8503/11 MN05013002Z-ENSwitching on when the gateway target configurationis storedIf a configuration is stored in the gateway, each time thesupply voltage is switched on it is checked whether theslaves actually found on the network comply with the storedgateway target configuration. The result of the check isdisplayed via the SmartWire-DT status LED on the gateway:Creating field bus communicationIf a data interchange is possible between the SmartWire-DTslaves and the gateway, in principle communicationbetween the gateway and the controller can also beperformed via CANopen.X Connect the CANopen gateway to the field bus.X Load the program into the PLC.Description Status SmartWire-DT LEDData interchangebetween the gateway andSmartWire-DT slavesThe current actual configuration complieswith the gateway target configuration.green continuous light yesA necessary SmartWire-DT slave ismissing or the coupling unit targetconfiguration does not comply with theactual configuration.flashing (red) noSlave addressing is active (after power onor the download of a planned configura-tion with empty modules).flashing (green) noShort-circuit on the 15 V power supply orno SmartWire-DT slave is connected.red continuous light no