2.6 Wiring power modulesPower modules are either integrated to the head module or may be installed between theperiphery modules. With power modules, terminals with spring clamp technology areused for wiring. The spring clamp technology allows quick and easy connection of yoursignal and supply lines. In contrast to screw terminal connections this type of connectionis vibration proof.Umax 30V DCImax 10ACross section 0.08 ... 1.5mm2 (AWG 28 ... 16)Stripping length 10mm1 Pin number at the connector2 Opening for screwdriver3 Connection hole for wire1. Insert a suited screwdriver at an angel into the square opening as shown. Pressand hold the screwdriver in the opposite direction to open the contact spring.2. Insert the stripped end of wire into the round opening. You can use wires with across section of 0.08mm2 up to 1.5mm23. By removing the screwdriver, the wire is securely fixed via the spring contact to theterminal.Terminal module terminalsDataWiring procedureVIPA System SLIO Basics and mountingWiring power modulesHB300 | FM | 054-1CB00 | en | 18-06 21