10 TroubleshootingYASKAWA SIEP C730600 89E PROFINET Technical Manual 51Code Name Causes Possible SolutionsoFA30 tooFA43 Option Card Connection Error(CN5-A) A fault occurred in the option. 1. De-energize the drive.2. Make sure that the option is correctly connected to theconnector.3. If the problem continues, replace the option.oFb00 Option Not Compatible with Port The option connected to connector CN5-B is notcompatible. Connect the option to the correct connector.• Use connector CN5-A when you connect the option.To use other options, refer to those option manuals.oFb02 Option Fault An option of the same type is already installed inoption port CN5-A, CN5-B, or CN5-C. Connect the option to the correct option port.oFC00 Option Fault (CN5-B) The option connected to connector CN5-C is notcompatible. Connect the option to the correct connector.• Use connector CN5-A when you connect the option.To use other options, refer to those option manuals.oFC02 Option Fault An option of the same type is already installed inoption port CN5-A, CN5-B, or CN5-C.Connect the option to the correct option port.◆ Option Fault Monitors U6-98 and U6-99The option can declare error/warning conditions via drive monitor parameters on the drive keypad as shown inTable 10.1.Table 10.1 Option Fault Monitor DescriptionsFault Condition Fault Declared StatusValue (U6-98/U6-99)DescriptionNo Fault N/A 0 No FaultForce Fault EF0 3 Network sent a message to force this node to the fault state.Network Link Down bUS 1300 No network link to option board.Network Failure bUS 1301 Connection with PLC Timeout.Default MAC Address None 1303 Factory default MAC Address programmed into the option. Return for reprogramming.No IP Address None 1304 No IP Address has been programmed into the option.No Station Name None 1305 No Station Name has been programmed into the option.Bad Station Name Programmed None 1306 Station Name Programmed is invalid and must be reprogrammed.Init. Failure None 1307 Initialize error on power-up.Permanent Communication Loss bUS 1308 Fatal error in MAC/PHY hardware Cycle power.Bad IP Configuration None 1309 Invalid IP/subnet/gateway address programmed into F7-01 - F7-12.Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:• U6-98: Shows the first declared fault since the last power cycle. Only cleared upon drive power-up.• U6-99: Shows the present option SI-EP3 status. Cleared upon a network-issued fault reset and upon power-up.If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value andU6-99 stores the new fault status value.◆ Option CompatibilityYou can connect a maximum of 3 options at the same time depending on the type of option.Note:You can only connect one option to the GA500 and HV600. Connect the option to the CN5 connector.Table 10.2 Option CompatibilityOption Connector Number of Options PossiblePG-B3, PG-X3 CN5-B, C 2 *1PG-RT3 *2 *3, PG-F3 *2 *3 CN5-C 1DO-A3, AO-A3 CN5-A, B, and C 1SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,SI-ES3, SI-B3, SI-M3,SI-W3 *3, SI-EM3 *3, SI-EN3 *3, SI-EP3,AI-A3 *4, DI-A3 *4CN5-A 1*1 To connect two PG options, use the CN5-C and CN5-B connectors. To connect only one PG option, use the CN5-C connector.