4.6 Application SelectionSeveral Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of theseApplication Presets automatically assigns functions to the input and output terminals, and sets certain parameters to valuesappropriate for the application that was selected.Note: An Application Preset can only be selected if all drive parameters are on at their original default settings. It may be necessary to initializethe drive by setting Z1-01 to 1 or 3 prior to selecting an Application Preset.WARNING! Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change theI/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.No. Parameter Name Setting Range DefaultA1-06 Application Presets0: Standard1: Fan2: Fan with PI Control3: Return Fan with PI Control4: Cooling Tower Fan5: Cooling Tower Fan with PI Control6: Pump (Secondary)7: Pump with PI Control0u Setting 1: Fan ApplicationTable 4.6 Fan: Parameter SettingsNo. Name Default Settingb1-03 Stopping Method Selection 1: Coast to Stopb1-04 Reverse Operation Selection 1: Reverse operation disabledC1-01 Acceleration Time 1 60 sL5-01 Number of Auto Restart Attempts 10L6-01 Torque Detection Selection 1 5: UL3 at speed agree (Alarm)u Setting 2: Fan with PI Control ApplicationTable 4.7 Fan with PI Control: Parameter SettingsNo. Parameter Name Default Settingb1-03 Stopping Method Selection 1: Coast to Stopb1-04 Reverse Operation Selection 1: Reverse operation disabledb5-01 PI Function Setting 1: Output frequency = PI output 1b5-03 Integral Time Setting (I) 30 sb5-08 PI Primary Delay Time Constant 2 sb5-13 PI Feedback Low Detection Level 2%b5-14 PI Feedback Low Detection Time 25 sC1-01 Acceleration Time 1 60 sL5-01 Number of Auto Restart Attempts 10L6-01 Stall Prevention Selection during Deceleration 5: UL3 at speed agree (Alarm)u Setting 3: Return Fan with PI Control ApplicationTable 4.8 Return Fan with PI Control: Parameter SettingsNo. Parameter Name Default Settingb1-03 Stopping Method Selection 1: Coast to Stopb1-04 Reverse Operation Selection 1: Reverse operation disabledb5-01 PI Function Setting 1: Output frequency = PI output 1b5-03 Integral Time Setting (I) 30 sb5-08 PI Primary Delay Time Constant 2 sb5-13 PI Feedback Low Detection Level 2%b5-14 PI Feedback Low Detection Time 25 s4.6 Application Selection108 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual