Z1000 BypassModel Z1B1 With Option PM Circuit Breaker CB1 Standard Non-Fused Input Disconnect Switch S1208Vac 480Vac Current Rating(A) Wire Size Range(AWG) TighteningTorque (lb. in.) Current Rating(A) Wire Size Range(AWG) TighteningTorque (lb. in.)D211 – 400 (1-2) x(2/0-500 kcmil) (1-2) x 442 400 (1-2) x(2/0-500 kcmil) (1-2) x 442D273 B240 600 (1-2) x(2/0-500 kcmil) (1-2) x 442– B302 600Table 3.3 Motor and Ground Wire Gauges and Tightening TorquesZ1000 BypassModel Z1B1Output Circuit Motor Wiring Earth Ground WiringMotor Overload Relay Ground Lug208 Vac 480 Vac Wire Size Range (AWG) Tightening Torque(lb. in.) Wire Size Range (AWG) Tightening Torque(lb. in.)– B00118-8 1514-10 or 8 or 6-4 or 2 35 or 40 or 45 or 50D002 B002D003 B003D004 B004D007 B007D010 B011D016 B014D024 B021D030 B027– B03416-2 70– B040– B52LD046 –D059 –– B052D074 B065 10-1/0 100– B077D088 B0966-3/0 200D114 B124D143 –D169 B156 6-300 kcmil 275– B180D211 B240(1-2) x (2/0-600 kcmil) (1-2) x 500 14-2/0 120D273 –– B302u Main Input Circuit and Motor WiringThis section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.WARNING! Electrical Shock Hazard. Do not connect the AC power line to the bypass output terminals. Failure to comply could result indeath or serious injury by fire as a result of bypass damage from line voltage application to output terminals.NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure tocomply may result in abnormal operation of drive and nearby equipment.NOTICE: When connecting the motor to the output terminals T1, T2, and T3, the phase order for the drive and motor should match. Failureto comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Failure to comply could result in damageto the drive, phase-advancing capacitors, LC/RC noise filters or ground fault circuit interrupters.3.4 Input and Output Power Wiring ConnectionsYASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual 633 Electrical Installation