u Setting 6: Pump (Secondary) ApplicationTable 4.11 Pump (Secondary): Parameter SettingsNo. Parameter Name Default Settingb1-04 Reverse Operation Selection 1: Reverse operation disabledC1-01 Acceleration Time 1 20 sd2-03 Master Speed Reference Lower Limit 20%L5-01 Number of Auto Restart Attempts 10L6-01 Stall Prevention Selection during Deceleration 5: UL3 at speed agree (Alarm)u Setting 7: Pump with PI Control ApplicationTable 4.12 Pump with PI Control: Parameter SettingsNo. Parameter Name Default Settingb1-04 Reverse Operation Selection 1: Reverse operation disabledb5-01 PI Function Setting 1: Enabled (PI output becomes output frequency reference)b5-03 Integral Time Setting (I) 15 sb5-08 PI Primary Delay Time Constant 10.0 sb5-13 PI Feedback Low Detection Level 2%b5-14 PI Feedback Low Detection Time 25 sb5-15 PI Sleep Function Start Level 72%b5-16 PI Sleep Delay Time 25.5 sC1-01 Acceleration Time 1 20 sd2-03 Master Speed Reference Lower Limit 20%L5-01 Number of Auto Restart Attempts 10L6-01 Stall Prevention Selection during Deceleration 5: UL3 at speed agree (Alarm)4.6 Application Selection110 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual