A.5 Bypass OptionsThis following configurations are available for the Z1000 Bypass.u Option BThree-contactor bypass: Isolates the drive circuit by adding a separate drive input contactor.u Option DEthernet/IP option.u Option MMotor Circuit Protector (MCP)/Disconnect: Replaces the standard input disconnect switch and provides short circuit protectionintegral with the drive and bypass package. The MCP includes a feature to padlock the operator mechanism through the door.Without this option, short circuit protection must be provided by others on the input side of the drive and bypass.u Option GDrive Input Disconnect Switch: Provides a disconnect means for the input side of the Drive, for Drive isolation capabilityduring bypass operation. This disconnect is located inside the enclosure with an integral operating handle.u Option LSerial Communication, Echelon LonWorks: An isolated circuit board provides LonTalk protocol for network communicationto a BAS. This option plugs into the CN5 connection on the bypass control circuit board.u Option WCustom Nameplate: Provides a custom nameplate for placement on the front of the Z1000 Bypass.A.5 Bypass OptionsYASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual 309A Specifications