u Bypass Analog OutputsThere are two analog outputs that can be configured for a signal level of 0 to 10 Vdc or 4 to 20 mA. The signal level is controlledby the position of jumpers J2 and J3 on Control PCB A2 and by the values set to drive parameters H4-07 and H4-08.u Serial CommunicationsRefer to BACnet Communications on page 359 or Refer to MEMOBUS/Modbus Communications on page 379 for detailsdepending on the applicable serial communications protocol.n Serial Communication TerminalsTable 3.9 Control Circuit Terminals: Serial CommunicationsType Name Description NotesMEMOBUS/Modbus orBACnetCommunicationIG5 Isolated groundGround reference for RS-485 signals. This is an isolated groundused only for communications and may be used in certaincircumstances to connect to other communication devices floatingground references.TXRX+ (+) Differential communication signal RS-485 signal levelsTXRX- (-) Differential communication signalSHIELD Shield tie point Connected to chassis groundn Bypass and Drive Control Circuit Wire Size and Torque SpecificationsSelect appropriate wire type and gauges from Table 3.10. For simpler and more reliable wiring, use crimp ferrules on the wireends. Refer to Table 3.11 for ferrule terminal types and sizes.Table 3.10 Bypass and Drive Control Circuit Gauge and Torque ValuesTerminal ScrewSizeTighteningTorqueN•m(lb. in)Bare Wire Terminal Ferrule-Type TerminalWire TypeApplicablewire sizemm2 (AWG)Recomm.wire sizemm2 (AWG)Applicablewire sizemm2 (AWG)Recomm.wire sizemm2 (AWG)DO-7, DO-8, DO-9,DO-10DI-1, DI-2, DI-3, DI-4,DI-5, DI-6, DI-7, DI-8,IG24IG5, TXRX+, TXRX-,SHIELDM3 0.5 to 0.6(4.4 to 5.3)Stranded wire:0.2 to 1.0(24 to 16)Solid wire:0.2 to 1.5(24 to 16)0.75 (18) 0.25 to 0.5(24 to 20) 0.5 (20) Shielded wire,etc.+V, A1, A2, ACFM, AM, ACR+, R-, S+, S-, IG M3 0.5 to 0.6(4.4 to 5.3)Stranded wire:0.2 to 1.0(24 to 16)Solid wire:0.2 to 1.5(24 to 16)0.75 (18) 0.25 to 0.5(24 to 20) 0.5 (20) Shielded wire,etc.n Ferrule-Type Wire TerminalsYaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire endswith insulated sleeves before connecting to the drive. See Table 3.11 for dimensions.d1d2 8 mmL(0.31 in.)Figure 3.21 Ferrule Dimensions3.5 Control Circuit Wiring72 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual