5.7 F: Optionsu F6: Drive/Bypass Communicationsn F6-01: Communications Error Operation SelectionDetermines drive operation when a communication error occurs.No. Parameter Name Setting Range DefaultF6-01 Communications Error Operation Selection 0 to 5 1Setting 0: Ramp to Stop (Use the Deceleration Time Set to C1-02)Setting 1: Coast to StopSetting 2: Fast Stop (Use the Fast Stop Time Set to C1-09)Setting 3: Alarm Only (Continue Operation)Setting 4: Alarm Only (Continue Operation Using the Frequency Reference Set in d1-04)Setting 5: Alarm Only (Use the Deceleration Time Set to C1-02)n F6-02: External Fault from Bypass Controller Detection SelectionDetermines the detection method of an external fault initiated by the bypass controller (EF0).No. Parameter Name Setting Range DefaultF6-02 External Fault from Bypass Controller Detection Selection 0, 1 0Setting 0: Always detectedSetting 1: Detection during Run onlyn F6-03: External Fault from Bypass Controller Operation SelectionDetermines drive operation when an external fault is initiated by the bypass controller (EF0).No. Parameter Name Setting Range DefaultF6-03 External Fault from Bypass Controller Operation Selection 0 to 3 1Setting 0: Ramp to stopSetting 1: Coast to stopSetting 2: Fast StopSetting 3: Alarm only (continue operation)5.7 F: Options150 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual