No.(Addr.Hex) Name Description Analog OutputLevel UnitU4-18(7DA)Frequency ReferenceSource SelectionReference SourceDisplays the source for the frequency reference as XY-nn.X: indicates which reference is used:0 = OFF1 = AUTO2 = HANDY-nn: indicates the reference source0-01 = HOA keypad1-00 = Analog (not assigned)1-01 = Analog (terminal A1)1-02 = Analog (terminal A2)2-02 to 17 = Multi-step speed (d1-02 to 17)3-01 = MEMOBUS/Modbus communications4-01 = Communication option card9-01 = Up/DownNo signal outputavailable –U4-19(7DB)Frequency Reference fromMEMOBUS/ModbusComm.MEMOBUS Freq RefDisplays the frequency reference provided by MEMOBUS/Modbus(decimal). No signal outputavailable 0.01%U4-20(7DC)Option FrequencyReferenceOption Freq RefDisplays the frequency reference input by an option card (decimal). No signal outputavailable –U4-21(7DD)Run Command SourceSelectionRun Cmd SourceDisplays the source for the Run command as XY-nn.X: Indicates which Run source is used:0 = OFF1 = AUTO2 = HANDY: Input power supply data0 = HOA keypad1 = External terminals3 = BACnet or MEMOBUS/Modbus communications4 = Communication option cardnn: Run command limit status data00: No limit status.01: Run command was left on when stopped in the PRG mode02: Run command was left on when switching from LOCAL to REMOTEoperation03: Waiting for soft charge bypass contactor after power up (Uv or Uv1flashes after 10 s)04: Waiting for “Run command prohibited” time period to end05: Fast Stop (digital input, HOA keypad)06: b1-17 (Run command given at power-up)07: During baseblock while coast to stop with timer08: Frequency reference is below minimal reference during baseblock09: Waiting for Enter commandNo signal outputavailable –U4-22(7DE)MEMOBUS/ModbusCommunicationsReferenceMEMOBUS Ref RegDisplays the drive control data set by MEMOBUS/Modbuscommunications register no. 0001H as a four-digit hexadecimal number. No signal outputavailable –U4-23(7DF)Communication OptionCard ReferenceOption Ref RegDisplays drive control data set by an option card as a four-digit hexadecimalnumber. No signal outputavailable –<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.u U5: PI MonitorsNo.(Addr.Hex) Name Description Analog OutputLevel UnitU5-01(57)PI FeedbackPI Feedback 1Displays the PI feedback value. 10 V: 100% 0.01%U5-02(63)PI InputPI InputDisplays the amount of PI input (deviation between PI setpoint andfeedback). 10 V: 100% 0.01%U5-03(64)PI OutputPI OutputDisplays PI control output. 10 V: 100% 0.01%U5-04(65)PI SetpointPI SetpointDisplays the PI setpoint. 10 V: 100% 0.01%B.13 U: MonitorsYASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual 345B Parameter List