B.15 Defaults by Drive ModelThe following tables show parameters and default settings that change with the drive model selection (o2-04).Table B.4 208 V Default Settings by Model SelectionNo. Name Unit Default Settings– Bypass Model Z1B1 –D002D003D004D007D010D016 D024 D031 D046 D059 D075o2-04 Drive Model Selection Hex. 66 68 6A 6B 6D 6E 6Fb3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 100b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.5 0.5b3-08 Current Control Gain during Speed Search(Speed Estimation Type) – 0.50 0.50 0.50 0.50 0.50 0.50 0.50b3-11 Speed Search Method Switching Level (SpeedEstimation Type) – 5.0 5.0 5.0 5.0 5.0 5.0 5.0C6-02 Carrier Frequency Selection – 2 2 2 2 2 2 2E2-01 Motor Rated Current A 10.60 16.70 24.20 30.80 46.2 59.4 74.8E2-03 Motor No-Load Current A 3.00 4.50 5.10 8.00 11.2 15.2 15.7L2-03 Momentary Power Loss Minimum BaseblockTime s 0.5 0.6 0.7 0.8 0.9 1 1L2-05 Undervoltage Detection Level (Uv1) – 190 190 190 190 190 190 190L8-02 Overheat Alarm Level °C 80 80 105 105 110 110 115L8-06 Input Phase Detection Level – 16.0 21.0 15.0 18.0 22.0 23.0 24.0L8-09 Output Ground Fault Detection Selection – 0 0 0 0 0 0 1L8-38 Carrier Frequency Reduction – 2 2 2 2 2 2 2No. Name Unit Default Settings– Bypass Model Z1B1 – D088 D114 D143 D169 D211 D273o2-04 Drive Model Selection Hex. 70 72 73 74 75 76b3-04 V/f Gain during Speed Search % 100 80 80 80 80 80b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.7b3-08 Current Control Gain during Speed Search (SpeedEstimation Type) – 0.50 0.50 0.50 0.50 0.50 0.50b3-11 Speed Search Method Switching Level (SpeedEstimation Type) – 5.0 5.0 5.0 5.0 5.0 5.0C6-02 Carrier Frequency Selection – 2 2 2 2 2 2E2-01 Motor Rated Current A 88 114 143 169 211 273E2-03 Motor No-Load Current A 18.5 21.9 38.2 44.0 45.6 72.0L2-03 Momentary Power Loss Minimum Baseblock Time s 1 1.1 1.1 1.2 1.3 1.5L2-05 Undervoltage Detection Level (Uv1) – 190 190 190 190 190 190L8-02 Overheat Alarm Level °C 115 115 109 109 109 109L8-06 Input Phase Detection Level – 24.0 25.0 28.0 26.0 28.0 28.0L8-09 Output Ground Fault Detection Selection – 1 1 1 1 1 1L8-38 Carrier Frequency Reduction – 2 2 2 2 2 2B.15 Defaults by Drive Model356 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual