D.9 MEMOBUS/Modbus Data TableThe tables below list all MEMOBUS/Modbus data.The MEMOBUS register hex addresses for parameters are listed beginning on page 313.u Command DataIt is possible to both read and write command data.Note: Bits that are not used should be set to 0. Refrain from writing to reserved registers.Register No. Contents0000H Reserved0001HOperation Commands and Multi-function Inputsbit 0 Reservedbit 1 Reservedbit 2 External Fault (EF0)bit 3 Fault Resetbit 4 Reservedbit 5 Reservedbit 6 Multi-Function Input 3bit 7 Multi-Function Input 4bit 8 Multi-Function Input 5bit 9 Multi-Function Input 6bit A Multi-Function Input 7bit B to F Reserved0002H Reserved Reserved0003H V/f Gain0004H, 0005H Reserved0006H PI Target, 0.01% units, signed0007H Analog Output Terminal FM Setting (10 V / 4000 H)0008H Analog Output Terminal AM Setting (10 V / 4000 H)0009HSettings for Multi-Function Digital Outputsbit 0 Multi-Function Contact Output 1 (terminal M1-M2)bit 1 Multi-Function Contact Output 2 (terminal M3-M4)bit 2 Multi-Function Contact Output 3 (terminal M5-M6)bit 3 to 5 Reservedbit 6 Enables the function in bit 7bit 7 Fault Contact Output (terminal MA/MB-MC)bit 8 to F Reserved000AH to 000CH Reserved000DH PI2 Setpoint000EH Reserved000FHControl Selection Settingbit 0 Reservedbit 1 PI Setpoint Inputbit 2, bit 3 Reservedbit 4 PI2 Target Input (enables the setting from MEMOBUS/Modbus)bit 5 to B Reservedbit C Enable Terminal S5 Input for Broadcast Databit D Enable Terminal S6 Input for Broadcast Databit E Enable Terminal S7 Input for Broadcast Databit F ReservedD.9 MEMOBUS/Modbus Data Table392 YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual