Table 3.14 Parameters H3-01 and H3-09 DetailsNo. Parameter Name Description SettingRange DefaultSettingH3-01 Terminal A1 signal level selectionSelects the signal level for terminal A1.0: 0 to 10 V with Zero Limit1: 0 to 10 V without Zero Limit2: 4 to 20 mA Current Input3: 0 to 20 mA Current Input0 to 3 0H3-09 Terminal A2 signal level selectionSelects the signal level for terminal A2.0: 0 to 10 V with Zero Limit1: 0 to 10 V without Zero Limit2: 4 to 20 mA Current Input3: 0 to 20 mA Current Input0 to 3 0u Terminal FM/AM Signal SelectionThe signal type for terminals FM and AM can be set to either voltage or current output using jumper S5 on the terminal boardas explained in Table 3.15. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.The default selection is voltage output for both terminals.Table 3.15 Jumper S5 SettingsTerminal Voltage Output Current OutputTerminal FMAMFMVIAMFMVITerminal AMAMFMVIAMFMVITable 3.16 Parameter H4-07 and H4-08 DetailsNo. Parameter Name Description SettingRange DefaultSettingH4-07 Terminal FM signal level selection 0: 0 to 10 Vdc2: 4 to 20 mA 0, 2 0H4-08 Terminal AM signal level selectionu MEMOBUS/Modbus TerminationThis drive is equipped with a built-in termination resistor for the RS-422/RS-485 communication connector. DIP switch S2enables or disabled the termination resistor as shown in Table 3.17. The OFF position is the default. The termination resistorshould be placed to the ON position when the drive is the last in a series of slave drives. Refer to Switches and Jumpers onthe Control Board on page 99 to locate switch S2.Table 3.17 MEMOBUS/Modbus Termination Switch S2 SettingsS2 Position DescriptionON Internal termination resistor ONOFF Internal termination resistor OFF (default setting)3.10 Control I/O ConnectionsYASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual 1013 Electrical Installation