Cause Possible SolutionsFrequency reference value is too low or the drive doesnot accept the value entered. Enter a value that is above the minimum output frequency determined by E1-09.The sequence Start/Stop sequence is set upincorrectly.• If the drive is supposed to be set up for a 2-wire sequence, then ensure parameters H1-03 throughH1-07 are not set to 0.• If the drive is supposed to be set up for a 3-wire sequence, then one of the parameters H1-03through H1-07 must be set to 0. Terminal S1 will become the Start, terminal S2 will become theStop input.n Motor Rotates in the Opposite Direction from the Run CommandCause Possible SolutionsPhase wiring between the drive and motor is incorrect.• Check the motor wiring.• Switch two motor cables (U, V, and W) to reverse motor direction.• Connect drive output terminals U/T1, V/T2, and W/T3 in the right order to match motorterminals U, V, and W.• Change the setting of parameter b1-14.The forward direction for the motor is set up incorrectly.Typically, forward is designated as being counterclockwise when looking from the motor shaft(see figure below).121. Forward Rotating Motor (looking down the motor shaft)2. Motor ShaftThe motor is running at almost 0 Hz and the SpeedSearch estimated the speed to be in the oppositedirection.• Disable bi-directional search (b3-14 = 0) so that Speed Search is performed only in thespecified direction.Note: Check the motor specifications for the forward and reverse directions. The motor specifications will vary depending on the manufacturerof the motor.n Motor Rotates in One Direction OnlyCause Possible SolutionsThe drive prohibits reverse rotation. • Check parameter b1-04.• Set parameter b1-04 to 0 to allow the motor to rotate in reverse.A Reverse run signal has not been entered, although3-Wire sequence is selected. • Make sure that one of the input terminals S3 to S7 used for the 3-Wire sequence has been setfor reverse.u Motor is Too HotCause Possible SolutionsThe load is too heavy.If the load is too heavy for the motor, the motor will overheat as it exceeds its rated torque valuefor an extended period of time.Keep in mind that the motor also has a short-term overload rating in addition to the possiblesolutions provided below:• Reduce the load.• Increase the acceleration and deceleration times.• Check the values set for the motor protection (L1-01, L1-02) as well as the motor rated current(E2-01).• Increase motor capacity.The air around the motor is too hot. • Check the ambient temperature.• Cool the area until it is within the specified temperature range.Insufficient voltage insulation between motor phases.When the motor cable is long, high voltage surges occur between the motor coils and driveswitching.Normally, surges can reach up to three times the drive input power supply voltage.• Use a motor with a voltage tolerance higher than the max voltage surge.• Use an inverter-duty motor rated for use with AC drives when using the motor on drives ratedhigher than 200 V class.• Install an AC reactor on the output side of the drive. The carrier frequency should be set to 2kHz when installing an AC reactor.5.10 Troubleshooting without Fault DisplayYASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual 2395 Troubleshooting