H2 Multi-Function Digital Output SettingsH2-ooSetting Function LCD Display Description Page100 to1B2Function 0 to b2 withinverse outputNote: A prefix of "!" isadded to representinverse functions on theLCD keypad display.Example: “!Zero speed”–Inverts the output switching of the multi-function output functions.Set the last two digits of 1oo to reverse the output signal of that specific function.–u H3: Multi-Function Analog InputsNo.(Addr.Hex) Name LCD Display Description Values PageH3-01(410) Terminal A1 SignalLevel SelectionTerm A1 Level0: 0-10V,(LowLim=0)1: 0-10V, (BipolRef)2: 4-20 mA3: 0-20 mA0: 0 to 10 V with zero limit1: 0 to 10 V without zero limit2: 4-20 mA3: 0-20 mANote: Use jumper switch S1 to set input terminal A1for current or voltage.Default: 0Range: 0 to 3 176H3-02(434) Terminal A1 FunctionSelection Term A1 FuncSel Sets the function of terminal A1. Default: 0Range: 0 to 26 177H3-03(411) Terminal A1 GainSetting Terminal A1 GainSets the level of the input value selected in H3-02 when 10 Vis input at terminal A1. Default: 100.0%Min.: -999.9Max.: 999.9 137H3-04(412) Terminal A1 BiasSetting Terminal A1 BiasSets the level of the input value selected in H3-02 when 0 V isinput at terminal A1. Default: 0.0%Min.: -999.9Max.: 999.9 137H3-09(417) Terminal A2 SignalLevel SelectionTerm A2 Level0: 0-10V,(LowLim=0)1: 0-10V, (BipolRef)2: 4-20 mA3: 0-20 mA0: 0 to 10 V with zero limit1: 0 to 10 V without zero limit2: 4 to 20 mA3: 0 to 20 mANote: Use jumper switch S1 to set input terminal A2for current or voltage input signal.Default: 2Range: 0 to 3 177H3-10(418) Terminal A2 FunctionSelection Term A2 FuncSel Sets the function of terminal A2. Default: 0Range: 0 to 26 177H3-11(419) Terminal A2 GainSetting Terminal A2 GainSets the level of the input value selected in H3-10 when 10 V(20 mA) is input at terminal A2. Default: 100.0%Min.: -999.9Max.: 999.9 137H3-12(41A) Terminal A2 BiasSetting Terminal A2 BiasSets the level of the input value selected in H3-10 when 0 V (0or 4 mA) is input at terminal A2. Default: 0.0%Min.: -999.9Max.: 999.9 137H3-13(41B) Analog Input Filter TimeConstant A1/A2 Filter T Sets a primary delay filter time constant for terminals A1 andA2. Used for noise filtering. Default: 0.03 sMin.: 0.00Max.: 2.00 –H3-14(41C) Analog Input TerminalEnable SelectionA1/A2 Sel1: A1 Available2: A2 Available3: A1/A2 AvailableDetermines which analog input terminals will be enabled whena digital input programmed for “Analog input enable”(H1-oo = C) is activated.1: Terminal A1 only2: Terminal A2 only3: Terminals A1 and A2Default: 2Range: 1 to 3 –H3-16(2F0) Terminal A1 Offset Term A1 Offset Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0Min.: -500Max.: 500 –H3-17(2F1) Terminal A2 Offset Term A2 Offset Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0Min.: -500Max.: 500 –B.7 H Parameters: Multi-Function Terminals308 YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual