u Wiring the Control Circuit TerminalThis section describes the proper procedures and preparations for wiring the control terminals.WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could resultin death or serious injury.NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, -M, +M, -, +1, +3, U/T1, V/T2, W/T3) and otherhigh-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.NOTICE: Separate wiring for digital output terminals MA, MB, MC, and M1 to M6 from wiring to other control circuit lines. Improper wiringpractices could result in drive or equipment malfunction or nuisance trips.NOTICE: Use a class 2 power supply when connecting to the control terminals. Improper application of peripheral devices could result indrive performance degradation due to improper power supply. Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control,Signaling, and Power Limited Circuits for requirements concerning class 2 power supplies.NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices couldresult in drive or equipment malfunction due to short circuit.NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive orequipment malfunction or nuisance trips.Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete. Refer toTerminal Wiring Guide on page 95 for details. Prepare the ends of the control circuit wiring as shown in Figure 3.46.Refer to Wire Gauges on page 93.NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may result in erroneous operation, damage to theterminal block, or cause a fire.NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive orequipment malfunction due to electrical interference.Connect control wires as shown in Figure 3.40 and Figure 3.41.Yaskawa recommends Phoenix Contact screwdriver model SZF 0-0.4 x 2.5 or equivalent to wire the terminal block.ABCDPreparing wireterminal ends0.4 2.5A – Loosen screw to insert wire.B – Single wire or stranded wireC – Avoid fraying wire strands whenstripping insulation from wire. Striplength 5.5 mm.D – Blade depth of 0.4 mm or lessBlade width of 2.5 mm or lessFigure 3.40 Terminal Wiring GuideUse the cable tie holes and cable hooks when wiring control terminals.Note: Take proper precautions when wiring the cables so that the front covers will easily fit back onto the drive. Make sure cables are not pinchedbetween the front covers and the drive when replacing the covers.3.9 Control Circuit WiringYASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual 953 Electrical Installation