3.3 Main Circuit Connection DiagramRefer to Figure 3.2 through Figure 3.8 when wiring the main circuit of the drive. Connections may vary based on drivecapacity. The DC power supply for the main circuit also provides power to the control circuit.u Three-Phase 200 V Class (2A0011 to 2A0273)Three-Phase 400 V Class (4A0005 to 4A0302)DriveMotor+MR/L1S/L2T/L3U/T1V/T2W/T3-M3-Phase power supply200 to 240 Vac, 50 to 60 Hz380 to 480 Vac, 50 to 60 Hz12-Pulse/18-PulseRectification (Option) <1><1> +M and -M are for rectification options only. Do not use for dynamic braking or line-regeneration.Figure 3.2 Connecting Main Circuit Terminalsu Three-Phase 200 V Class (2A0343 and 2A0396)Three-Phase 400 V Class (4A0361 to 4A0590)12-Pulse/18-PulseRectification (Option) orDC power supply+3R/L1S/L2T/L3U/T1V/T2W/T3DriveMotor−Three-Phase power supply200 to 240 Vac, 50 to 60 Hz380 to 480 Vac, 50 to 60 Hz+ 1Figure 3.3 Connecting Main Circuit Terminalsu 12-Pulse/18-Pulse RectificationOperation with 12-pulse/18-pulse rectification requires the user to separately prepare a 3-winding/4-winding transformer forthe power supply. Contact Yaskawa or your nearest sales representative for the transformer specifications.n Wiring to –M/+M Terminals (2A0011 to 2A0273 and 4A0005 to 4A0302)Access the –M/+M terminals by cutting off the protection cover on models 2A0011 to 2A0114 and 4A0005 to 4A0096 or byremoving the protection sheet on –M/+M terminals on models 2A0143 to 2A0273 and 4A0124 to 4A0302.–M/+M are for rectification options only. Do not use for dynamic braking or line-regeneration.A AA –Protective covering over –M/+M terminalsFigure 3.4 –M/+M Terminals3.3 Main Circuit Connection DiagramYASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual 653 Electrical Installation