B.7 H Parameters: Multi-Function TerminalsH parameters assign functions to the multi-function input and output terminals.u H1: Multi-Function Digital InputsNo.(Addr.Hex) Name LCD Display Description Values PageH1-01(438)Multi-Function DigitalInput Terminal S1Function Selection Term S1 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 302 to 305 for descriptions of setting values.Note: Set unused terminals to F.Default: 40 (F)<1>Min.: 1Max.: B2–H1-02(439)Multi-Function DigitalInput Terminal S2Function Selection Term S2 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 302 to 305 for descriptions of setting values.Note: Set unused terminals to F.Default: 41 (F)<1>Min.: 1Max.: B2–H1-03(400)Multi-Function DigitalInput Terminal S3Function Selection Term S3 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 302 to 305 for descriptions of setting values.Note: Set unused terminals to F.Default: 24Min.: 0Max.: B2 –H1-04(401)Multi-Function DigitalInput Terminal S4Function Selection Term S4 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 302 to 305 for descriptions of setting values.Note: Set unused terminals to F.Default: 14Min.: 0Max.: B2 –H1-05(402)Multi-Function DigitalInput Terminal S5Function Selection Term S5 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 302 to 305 for descriptions of setting values.Note: Set unused terminals to F.Default: 3 (0) <1>Min.: 0Max.: B2–H1-06(403)Multi-Function DigitalInput Terminal S6Function Selection Term S6 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 302 to 305 for descriptions of setting values.Note: Set unused terminals to F.Default: 4 (3) <1>Min.: 0Max.: B2–H1-07(404)Multi-Function DigitalInput Terminal S7Function Selection Term S7 Func SelAssigns a function to the multi-function digital inputs.Refer to pages 302 to 305 for descriptions of setting values.Note: Set unused terminals to F.Default: 6 (4) <1>Min.: 0Max.: B2–<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).H1 Multi-Function Digital Input SelectionsH1-ooSetting Function LCD Display Description Page0 3-Wire sequence 3-Wire Control Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)Terminals S1 and S2 are automatically set up for the Run command and Stopcommand. –3 Multi-Step SpeedReference 1 Multi-Step Ref 1 When input terminals are set to Multi-Step Speed References 1 through 3,switching combinations of those terminals will create a multi-step speed sequenceusing the frequency references set in d1-01 through d1-04, and d1-16.–4 Multi-Step SpeedReference 2 Multi-Step Ref 2 When input terminals are set to Multi-Step Speed References 1 through 3,switching combinations of those terminals will create a multi-step speed sequenceusing the frequency references set in d1-01 through d1-04, and d1-16. –6 Jog reference selection jog Freq Ref Closed: Jog frequency reference (d1-17) selected. Jog has priority over all otherreference sources. –7 Accel/decel timeselection 1 Multi-Acc/Dec 1 Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/deceltime 2 (set in C1-03, C1-04). –8 Baseblock command(N.O.) Ext BaseBlk N.O. Closed: No drive output –9 Baseblock command(N.C.) Ext BaseBlk N.C. Open: No drive output –A Accel/decel ramp hold Acc/Dec RampHold Open: Accel/decel is not heldClosed: The drive pauses during acceleration or deceleration and maintains theoutput frequency. –B Drive overheat alarm(oH2) OH2 Alarm Signal Closed: An external device has triggered an oH2 alarm. –C Analog terminal inputselection Term AI Enable Open: Function assigned by H3-14 is disabled.Closed: Function assigned by H3-14 is enabled. –B.7 H Parameters: Multi-Function Terminals302 YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual