B.6 F: Communication Option Parametersu F6, F7: Communication Option CardParameters F6-01 through F6-03 and F6-06 through F6-08 are used for EtherNet/IP, Modbus TCP/IP, and LONWORKSoptions. F7 parameters are used for the EtherNet/IP and Modbus TCP/IP options.No.(Addr.Hex) Name LCD Display Description Values PageF6-01(3A2) Communications ErrorOperation SelectionComm Bus Flt Sel0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only4: Alarm (d1-04)5: Alarm (C1-02)0: Ramp to stop. Decelerate to stop using the deceleration timein C1-02.1: Coast to stop.2: Fast Stop. Decelerate to stop using the deceleration time inC1-09.3: Alarm only. <1>4: Alarm only. Continue operation using the frequencyreference set in d1-04. <1> <2>5: Alarm only. Decelerate to stop using the deceleration timein C1-02. <3> <4>Default: 1Range: 0 to 5 –F6-02(3A3)External Fault fromComm. OptionDetection SelectionEF0 Detection0: Always Detected1: Only During Run0: Always detected.1: Detection during run only. Default: 0Range: 0, 1 –F6-03(3A4)External Fault fromComm. OptionOperation SelectionEF0 Fault Action0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only0: Ramp to stop. Decelerate to stop using the deceleration timein C1-02.1: Coast to stop.2: Fast Stop. Decelerate to stop using the deceleration time inC1-09.3: Alarm only. <1>Default: 1Range: 0 to 3 –F6-06(3A7)Torque Reference/Torque Limit Selectionfrom Comm. OptionTorq Ref/Lmt Sel0: Disabled1: EnabledOLV/PMOLV/PM0: Disabled. Torque reference/limit from option board disabled.1: Enabled. Torque reference/limit from option board enabled.Default: 0Range: 0, 1 –F6-07(3A8)Multi-Step SpeedEnable/DisableSelection when NefRef/ComRef is SelectedFref PrioritySel0: Net/Com REF1: MultiStep Speed0: Multi-step reference disabled (same as F7)1: Multi-step reference enabled (same as V7) Default: 0Range: 0, 1 –F6-08(36A)<5>Reset CommunicationParametersCom Prm Init Sel0: Init Com Prms1: No Init Com Prms0: Communication-related parameters (F6-oo) are not resetwhen the drive is initialized using A1-03.1: Reset all communication-related parameters (F6-oo) whenthe drive is initialized using A1-03.Default: 0Range: 0, 1 –F6-14(03BB) CC-Link bUS ErrorAuto ResetBus Err Auto Rst0: Disabled1: Enabled0: Disabled1: Enabled Default: 0Range: 0, 1 –F6-46(02FC) BACnet Baud RateBAC Baud Rate0: 1200 bps1: 2400 bps2: 4800 bps3: 9600 bps4: 19.2 kbps5: 38.4 kbps6: 57.6 kbps7: 76.8 kbps8: 115.2 kbps0: 12001: 24002: 48003: 96004: 192005: 384006: 57600 <3>7: 76800 <3>8: 115200 <3>Default: 3Range: 0 to 8 –F7-01(3E5)<6> <7><8>IP Address 1 IP Address 1 Sets the most significant octet of network static IP address. Default: 192Min.: 0Max.: 255 –F7-02(3E6)<6> <7><8>IP Address 2 IP Address 2 Sets the second most significant octet of network static IPaddress.Default: 168Min.: 0Max.: 255 –F7-03(3E7)<6> <7><8>IP Address 3 IP Address 3 Sets the third most significant octet of network static IP address. Default: 1Min.: 0Max.: 255 –B.6 F: Communication Option ParametersYASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual 299B Parameter List