B.10 o: Operator-Related SettingsThe o parameters set up the HOA keypad displays.u o1: HOA Keypad Display SelectionNo.(Addr.Hex) Name LCD Display Description Values Pageo1-01(500) Drive Mode UnitMonitor Selection User Monitor SelSelects the content of the last monitor that is shown whenscrolling through Drive Mode display. Enter the last three digitsof the monitor parameter number to be displayed: Uo-oo.Default: 106Range: 104 to699 187o1-02(501) User Monitor Selectionafter Power UpPower-On Monitor1: Frequency Ref2: FWD/REV3: Output Freq4: Output Current5: User Monitor1: Frequency reference (U1-01)2: Direction3: Output frequency (U1-02)4: Output current (U1-03)5: User MonitorDefault: 1Range: 1 to 5 187o1-03(502) HOA Keypad DisplaySelectionDisplay Unit Sel0: 0.01 Hz1: 0.01%2: r/min3: User UnitsSets the units the drive should use to display the frequencyreference and motor speed monitors.0: 0.01 Hz1: 0.01% (100% = E1-04)2: r/min (calculated using the number of motor poles setting inE2-04, E4-04, or E5-04)3: User-selected units (set by o1-10 and o1-11)Default: 0Range: 0 to 3 188o1-06(517) User Monitor SelectionModeMonitor Mode Sel0: 3 Mon Sequential1: 3 Mon Selectable0: 3 Monitor Sequential(Displays the next two sequential monitors)1: 3 Monitor Selectable (o1-07 and o1-08 selected monitor areshown)Default: 0Range: 0, 1 188o1-07(518) Second Line MonitorSelection 2nd Monitor SelSelects the monitor that is shown in the second line.Enter the last three digits of the monitor parameter number tobe displayed: Uo-oo. For example, set "403" to displaymonitor parameter U4-03.Default: 102Range: 101 to699 188o1-08(519) Third Line MonitorSelection 3rd Monitor SelSelects the monitor that is shown in the third line.Enter the last three digits of the monitor parameter number tobe displayed: Uo-oo. For example, set "403" to displaymonitor parameter U4-03.Default: 103Range: 101 to699 188o1-09(51C) Frequency ReferenceDisplay UnitsFref Disp Unit0: WC1: PSI2: GPM3: °F4: CFM5: CMH6: LPH7: LPS8: Bar9: Pa10: °C11: Mtr12: Ft13: LPM14: CMM15: Custom unit16: No UnitSets unit display for the frequency reference parameters andfrequency related monitors when o1-03 = 3.0: WC (Inch of water)1: PSI (Pounds per square inch)2: GPM (Gallons per minute)3: F (Degrees Fahrenheit)4: CFM (Cubic feet per minute)5: CMH (Cubic meters per hour)6: LPH (Liters per hour)7: LPS (Liters per second)8: Bar (Bar)9: Pa (Pascal)10: C (Degrees Celsius)11: Mtr (Meters)12: Ft (Feet)13: LPM (Liters per minute)14: CMM (Cubic meters per minute)15: Custom units (Determined by o1-12)16: NoneDefault: 16Range: 0 to 16 188o1-10(520) User-Set Display UnitsMaximum Value UserDisp ScalingThese settings define the display values when o1-03 is set to 3.o1-10 sets the display value that is equal to the maximum outputfrequency.o1-11 sets the position of the decimal position.Default: <1>Range: 1 to60000189o1-11(521) User-Set Display UnitsDecimal Display UserDisp Dec Default: <1>Range: 0 to 3 189o1-13(3105)Frequency Referenceand Frequency RelatedMonitor Custom Units 1 Fref Cust Unit 1 Sets the customer-specified unit display for the frequencyreference parameters and frequency related monitors wheno1-03 = 3 and o1-09 = 15 as custom units.Default: 41Range: 30 to 7A 189o1-14(3106)Frequency Referenceand Frequency RelatedMonitor Custom Units 2 Fref Cust Unit 2 Sets the customer-specified unit display for the frequencyreference parameters and frequency related monitors wheno1-03 = 3 and o1-09 = 15 as custom unitsDefault: 41Range: 30 to 7A 189B.10 o: Operator-Related SettingsYASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual 321B Parameter List