CHAPTER 5: SETTINGS PRODUCT SETUPN60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL 5-435Figure 5-10: IEC 61850 protocol panel in EnerVista softwareThe IEC 61850 window is divided into a navigation pane on the left and a settings panel on the right. You expand and clickan option on the left to display its panel on the right. The following figure shows an example for Server Configuration. Thesetting entry panel contains in the SETTING column the names of the settings, and the settings entry boxes are in thePARAMETER column. Hovering the mouse over a setting name displays a tool-tip showing the 61850 information modelname of the setting or its location in SCL files.Figure 5-11: Main IEC 61850 panelOpening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from theconnected N60. This SCD file contains all the settings in the UR at the time of the file request, both those that are mappedinto the IEC 61850 information model (that is, the "public" sections) and those that are not in the model (that is, the "private"section). The UR Setup software imports all of these settings into the current session, not just those in the IEC 61850window. To avoid loss of any unsaved setting changes made in other panels during the current session, all other panels forthe N60 must be closed before the IEC 61850 panel can be opened; the software prompts for this when applicable. Panelsfor other devices can be open concurrently to facilitate parameter coordination.