CHAPTER 5: SETTINGS PRODUCT SETUPN60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL 5-595Buffered Report1 RptIDRange: 0 to 129 VisibleString charactersDefault: empty stringThe entered value sets the RptID value in Buffered Report1 messages, and it can be used by the client to discriminateBuffered Report1 messages from other messages. If the number of characters entered is zero, the value used for RptIDin messages is an ObjectReference to the report's control block, that is, "/LLN0$BR$"BRCB01".Buffered Report1 DatSetRange: None, DataSet01, DataSet02, …Default: NoneThis setting selects the data set whose members' status is reported in Buffered Report1 messages using the UR Setupsoftware designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, asdescribed later.An ObjectReference to the data set, which consists of the concatenation of the string "/LLN0$" and the dataset name, is used in the datSet field of report messages, and it can be used by the client to discriminate Buffered Report1messages from other messages.Buffered Report1 ConfRevRange: 0 to 4294967295 in steps of 1Default: 1The entered value sets the confRev value in Buffered Report1 messages, and it can be used by clients to discriminatereport messages of the expected configuration revision from messages of a different revision. The standard requiresthat confRef be incremented each time the members or the order of the members is changed, and each time the dataset name is changed. The standard states that the value of 0 is reserved.Buffered Report1 OptFldsRange: The check box for each individual bit can be enabled or not (see figure)Default: All bits trueThe OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The figureshows the available option bits.Figure 5-19: Options for buffered report messagesBuffered Report1 BufTmRange: 0 to 4294967295 in steps of 1Default: 0The entered value sets the time interval in milliseconds for the buffering of events for inclusion in a single report.