CHAPTER 5: SETTINGS PRODUCT SETUPN60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL 5-695CommandsThe UR implements a number of clear records commands as detailed in the Commands and Targets chapter of thismanual. Several of these commands also can be issued via IEC 61850. The settings related to these IEC 61850 commandsare described here.Navigate to Settings > Product Setup > Communications > IEC 61850 > Commands to access the settings that configurethe IEC 61850 protocol interface for record clear commands.Figure 5-26: Commands panelFltRptRFLO1.RsStat.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"here is select-before-operate. Enhanced security means that the N60 reports to the client the breaker 1 position at theend of the command sequence.LLN0.EvtRcdClr.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.LPHD1.RsStat.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.OscRDRE1.RcdTrg.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command FORCE TRIGGER.