5-170 N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUALGROUPED ELEMENTS CHAPTER 5: SETTINGS5Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when noother group is active.5.7.3 Power swing detectSETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) POWER SWING DETECT VOLTAGE ELEMENTSSee page 5-180 SUPERVISING ELEMENTSSee page 5-183 POWERSee page 5-185 POWER SWING DETECT POWER SWINGFUNCTION: DisabledRange: Disabled, Enabled POWER SWINGSOURCE: SRC 1Range: SRC 1, SRC 2 POWER SWINGSHAPE: Mho ShapeRange: Mho Shape, Quad Shape POWER SWINGMODE: Two StepRange: Two Step, Three Step POWER SWINGSUPV: 0.600 puRange: 0.050 to 30.000 pu in steps of 0.001 POWER SW I2 SUPV ENAB:OffRange: FlexLogic operand POWER SWINGI2 SUPV: 0.2 puRange: 0.050 to 30.000 pu in steps of 0.001 POWER SWING FWDREACH: 50.00 Range: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING QUAD FWDREACH MID: 60.00 Range: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING QUAD FWDREACH OUT: 70.00 Range: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING FWDRCA: 75°Range: 40 to 90° in steps of 1 POWER SWING REVREACH: 50.00 Range: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING QUAD REVREACH MID: 60.00 Range: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING QUAD REVREACH OUT: 70.00 Range: 0.10 to 500.00 ohms in steps of 0.01 POWER SWING REVRCA: 75°Range: 40 to 90° in steps of 1 POWER SWING OUTERLIMIT ANGLE: 120°Range: 40 to 140° in steps of 1 POWER SWING MIDDLELIMIT ANGLE: 90°Range: 40 to 140° in steps of 1 POWER SWING INNERLIMIT ANGLE: 60°Range: 40 to 140° in steps of 1