CHAPTER 5: SETTINGS SYSTEM SETUPN60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL 5-1395This element responds to elevated current. The trigger responds to the phase current signal of the Phasor MeasurementUnit (PMU) source. All current channel (A, B, and C) are processed independently and can trigger the recorder.PMU 1 CURR TRIGGER PICKUP — Specifies the pickup threshold for the overcurrent trigger, in per unit of the PMU source. Avalue of 1 pu is a nominal primary current. The comparator applies a 3% hysteresis.PMU 1 CURR TRIGGER PKP TIME — Use to filter out spurious conditions and avoid unnecessary triggering of the recorder.PMU 1 CURR TRIGGER DPO TIME — Use to extend the trigger after the situation returns to normal. This setting is ofimportance when using the recorder in the forced mode (recording as long as the triggering condition is asserted).Figure 5-61: Current trigger logic5.5.6.16 Power triggeringSETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PHASOR MEASUREMENT UNIT 1(6) PMU 1(6)TRIGGERING PMU 1(6) POWER TRIGGERThis element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. Interms of signaling its operation, the element does not differentiate among the three types of power. The trigger respondsto the single-phase and three-phase power signals of the Phasor Measurement Unit (PMU) source. PMU 1 CURR TRIGGEREVENTS: DisabledRange: Enabled, Disabled PMU 1 POWER TRIGGER PMU 1 POWER TRIGGERFUNCTION: DisabledRange: Enabled, Disabled PMU 1 POWER TRIGGERACTIVE: 1.250 puRange: 0.250 to 3.000 pu in steps of 0.001 PMU 1 POWER TRIGGERREACTIVE: 1.250 puRange: 0.250 to 3.000 pu in steps of 0.001 PMU 1 POWER TRIGGERAPPARENT: 1.250 puRange: 0.250 to 3.000 pu in steps of 0.001 PMU 1 POWER TRIGGERPKP TIME: 0.10 sRange: 0.00 to 600.00 s in steps of 0.01 PMU 1 POWER TRIGGERDPO TIME: 1.00 sRange: 0.00 to 600.00 s in steps of 0.01 PMU 1 PWR TRIG BLK:OffRange: FlexLogic operand PMU 1 POWER TRIGGERTARGET: Self-ResetRange: Self-Reset, Latched, Disabled PMU 1 POWER TRIGGEREVENTS: DisabledRange: Enabled, DisabledSETTINGSPMU 1 CURR TRIGGERFUNCTION:Enabled = 1PMU 1 CURR TRIG BLK:Off = 0SETTINGSPMU 1 SIGNALSOURCE:ANDSETTINGSPMU 1 CURR TRIGGER PICKUP:RUN SETTINGSPMU 1 CURR TRIGGER DPO TIME:tDPOFLEXLOGIC OPERANDPMU 1 CURR TRIGGERFLEXLOGIC OPERANDSPMU 1 FREQ TRIGGERPMU 1 VOLT TRIGGERPMU 1 POWER TRIGGERPMU 1 ROCOF TRIGGERSETTINGPMU 1 USER TRIGGER:Off = 0OR FLEXLOGIC OPERANDPMU 1 TRIGGEREDto STAT bits ofthe data frameIA I > PICKUPI > PICKUPI > PICKUPORIBIC 847010A1.CDRSETTINGSPKPt0PMU 1 CURR TRIGGER PKP TIME:0