5.4 Operator Programming Errorsu Operator Programming Error Codes, Causes, and Possible SolutionsAn Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to aninappropriate value.The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does nottrigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to Table 5.4 for the appropriate action. Whenan oPE appears on the operator display, press the ENTER button to view U1-18 and see which parameter is causing the oPE.Table 5.4 oPE Codes, Causes, and Possible SolutionsDigital Operator Display Error NameoPE01 Drive Capacity Setting FaultDrive capacity and the value set to o2-04 do not match.oPE02 Parameter Range Setting ErrorUse U1-18 to find parameters set outside the range.oPE03Multi-Function Input Selection ErrorA contradictory setting is assigned to multi-function contact inputs H1-01to H1-08.oPE04 Initialization requiredoPE05 Run Command/Frequency Reference Source Selection ErroroPE06 Control Method Selection ErrorCorrect the setting for the control method.oPE07Multi-Function Analog Input Selection ErrorA contradictory setting is assigned to multi-function analog inputs H3-02,H3-06, or H3-10 and PID functions conflict.oPE08Parameter Selection ErrorA function has been set that cannot be used in the motor control methodselected.oPE09PID Control Selection FaultPID control function selection is incorrect. Requires that PID control isenabled (b5-01 = 1 to 4).oPE10V/f Data Setting ErrorThe following setting errors have occurred where:• E1-04 is greater than or equal to E1-06, E1-06 is greater than or equal toE1-07, E1-07 is greater than or equal to E1-09, or E1-09 is greater thanor equal to E1-11.• E3-04 is greater than or equal to E3-06, E3-06 is greater than or equal toE3-07, E3-07 is greater than or equal to E3-09, or E3-09 is greater thanor equal to E3-11.oPE11 Carrier Frequency Setting ErrorCorrect the setting for the carrier frequency.oPE13 Pulse Monitor Selection ErrorIncorrect setting of monitor selection for pulse train (H6-06).oPE15Torque Control Setting ErrorParameters settings that are not allowed in combination with TorqueControl have been set.oPE16 Energy Savings Constants ErroroPE18 Online Tuning Parameter Setting ErrorParameters controlling online tuning are not set correctly.5.4 Operator Programming ErrorsYASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide 1435 Troubleshooting