u H6: Pulse Train Input/OutputNo.(Addr.Hex) Name Description Values PageH6-01(42C) Pulse Train Input TerminalRP Function Selection0: Frequency reference1: PID feedback value2: PID setpoint value3: V/f Control with Simple PG feedback (possible only when using motor 1in V/f Control)Default: 0Range: 0 to 3 –H6-02(42D) Pulse Train Input ScalingSets the terminal RP input signal frequency that is equal to 100% of the valueselected in H6-01. Default: 1440 HzMin.: 1000Max.: 32000 –H6-03(42E) Pulse Train Input GainSets the level of the value selected in H6-01 when a frequency with the valueset in H6-02 is input. Default: 100.0%Min.: 0.0Max.: 1000.0 –H6-04(42F) Pulse Train Input BiasSets the level of the value selected in H6-01 when 0 Hz is input. Default: 0.0%Min.: -100.0Max.: 100.0 –H6-05(430) Pulse Train Input Filter TimeSets the pulse train input filter time constant. Default: 0.10 sMin.: 0.00Max.: 2.00 –H6-06(431) Pulse Train MonitorSelectionSelect the pulse train monitor output function (value of the o-oo part ofUo-oo).For example, enter “501” for U5-01.Default: 102Range: 000 to 809 –H6-07(432) Pulse Train Monitor ScalingSets the terminal MP output signal frequency when the monitor value is 100%.To have the pulse train monitor output equal the output frequency, set H6-06to 2 and H6-07 to 0.Default: 1440 HzMin.: 0Max.: 32000 –H6-08(43F) Pulse Train Input MinimumFrequencySets the minimum frequency for the pulse train input to be detected. Enabledwhen H6-01 = 0, 1, or 2. Default: 0.5 HzMin.: 0.1Max.: 1000.0 –B.7 H Parameters: Multi-Function TerminalsYASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide 213B Parameter List